My pool heat pump trips the circuit when the compressor starts up.
Does your pool heat pump trip your electricity cabinet when it starts up? There are several possibilities:
For a newly installed heat pump:
- The meter trips: increase the limits of your energy plan with your energy supplier
- The circuit breaker trips: check that the right circuit breaker is installed and that the correct cable cross-section is used (refer to the heat pump manual).
For an older, previously-installed heat pump:
- The meter trips: increase the limits of your energy plan with your energy supplier.
- The circuit breaker trips: check the start-up condenser, it will probably need to be replaced. If this continues after the replacement, check that the correct circuit breaker has been installed and the correct cable cross-section is used (refer to the heat pump manual).
- The residual current circuit breaker trips: ask for a visit from a refrigeration specialist.